Item |
Specification |
Type |
EH-PT4 |
Temperature-sensing element |
Platinum resistance temperature detector Pt 100 (JIS C 1604-1989) / Pt 1000 |
Temperature conversion data |
Signed 15 bits |
Accuracy *1 |
-20°C to 40°C (Pt 100) |
±0.1°C @ 25°C ±0.5°C (0 to 55°C) |
-50°C to 400°C (Pt 100) |
±0.6°C @ 25°C ±3°C (0 to 55°C) |
-50°C to 400°C (Pt 1000) |
±0.8°C @ 25°C ±6°C (0 to 55°C) |
Temperature measuring range |
-20 to +40°C/ -50 to +400°C (2mA constant current system) |
Number of input points |
4 |
Conversion time |
Approximately 0.5 second per four inputs |
Insulation |
Between input and |
Photocoupler insulation |
internal circuit |
Between inputs |
No insulation |
Weight |
Approximately 0.15 kg (0.33lb.) |
External Connection |
Removal terminal block (M3) |
Unused terminal processing |
Unused terminals (for current, voltage and ground) should be shorted at the terminal block (Temperature conversion data for one of the four values is H7FFF) |
External wiring register |
The maximum total wiring resistance from current terminal to ground terminal is 2 Ω. |
External wiring |
3 cores shielded cable |
Additional function |
Linearization |
Resolution |
-20°C to 40°C (Pt100) |
0.0024°C |
-50°C to 400°C (Pt100) |
0.024°C |
-50°C to 400°C (Pt1000) |
0.024°C |
Internal current consumption (5V DC) |
Approximatly 160mA |
Externally supplied power |
24V DC±10%, Maximum current consumption is 70mA |