Irem |
Specification |
Power Voltage |
AC receiving power |
100/110/120V AC (50/60Hz), 200/220/240V AC (50/60Hz) |
DC receiving power |
24 V DC |
Power voltage fluctuation range |
85 to 264 V AC wide range |
21.6 to 26.4 V DC |
Allowable instantaneous power failure |
85 to 100V AC : for a momentary power failure of less than 10 ms, operation continues 100 to 264 V AC : for a momentary powr failure of less than 20 ms, operation continues |
Operating ambient temperature |
0 to 55 °C (Storage ambient temperature -10 to 75 °C) |
Operating ambient humidity |
20 to 90% RH (no ccondensation) (Storage ambient humidity 10 to 90% RH (no condensation)) |
Vibration resistance |
Conforming to IEC (EN) 61131-2 (147m/s2, 3times in each of 3 directions X, Y, Z) |
Noise resistance |
- Noise voltage 1,500Vpp Noise pulse width 100 ns, 1 µs (Noise created by the noise simulator is applied across the power supply module's input terminals. This is determined by this company's measuring methods.)
- Based on NEMA ICS3-304 (with the exception of input module)
- Static noise : 3,000V at metal exposed area
|
Insulation resistance |
20 MΩ or more between the AC external terminal and case ground (FE) terminal (based on 500V DC mega) |
Dielectric withstand voltage |
1,500V AC for 1 minute between the AC external terminal and case ground (FE) terminal |
Grounding |
Class D grounding (ground with power supply module) |
Usage environment |
No corrosive gases, no exceessive dust |
Structure |
Open, wall-mount type |
Cooling |
Natural air cooling |