| Item | 
10 point type | 
14 point type | 
23 point type | 
28 point type | 
 
| Control specifications | 
CPU | 
32-bit RISC processor | 
 
| Processing system | 
Stored program cyclic system | 
 
Processing Speed | 
Basic instructions | 
0.9 µs / instruction | 
 
| Application instructions | 
Several 10 µs / instruction | 
 
| User program memory | 
3 k steps max. (FLASH memory) | 
 
| Operation processing specifications | 
Instruction language | 
Basic instructions | 
39 types such as LD, LDI, AND, ANI, OR, ORI, ANB, ORB, OUT, MPS, MRD, MPP, etc. | 
 
Arithmetic instructions Application instructions | 
62 types (arithmetic, application, control, FUN command etc.) | 
 
| Ladder | 
Basic instructions | 
39 types, such as 
  | 
 
Arithmetic instructions Application instructions | 
62 types (arithmetic, application, control, FUN command etc.) | 
 
| I/O processing specifications | 
External I/O | 
I/O processing system | 
Refresh processing | 
 
| Maximum number of points | 
10 points | 
126 points | 
135 points | 
140 points | 
 
| Internal output | 
Bit | 
1,984 points (R0 to R7BF) | 
 
| Word | 
4,096 words (WR0 to WRFFF) | 
 
| Special | 
Bit | 
64 points (R7C0 to R7FF) | 
 
| Word | 
512 words (WRF000 to WRF1FF) | 
 
| Bit / Word shared | 
16,384 points, 1,024 words (M0 to M3FFF, WM0 to WM3FF) | 
 
| Timer counter | 
Number of points | 
256 points (TD+CU) *1 | 
 
| Timer set value | 
0 to 65,535, timer base 0.01 s, 0.1 s, 1 s (0.01s has maximum 64 points *2) | 
 
| Counter set value | 
1 to 65,535 times | 
 
| Edge detection | 
512 points (DIF0 to DIF511:Decimal) + 512 points (DFN0 to DFN511:Decimal) | 
 
| Peripheral equipment | 
Program system | 
Instruction language, ladder diagram | 
 
| Peripheral unit | 
Programming software (LADDER EDITOR DOS version/Windows® version, Pro-H) Instruction language programmer and form graphic display programmer cannot be used. | 
 
| Maintenance functions | 
Self-diagnosis | 
PLC error (LED display): Microcomputer error, watchdog timer error, memory error, program error, system ROM/RAM error, scan time monitoring, battery voltage low detection, etc. | 
 
 
 
- *1
 
- The same numbers cannot be used with the timer counter.
 
- *2
 
- Only timers numbered 0 to 63 can use 0.01 s for their timer base.
 
 
 
  
 
 
 
 
   |