10 point/14 point/23 point/28 point type Input / Output Specifications
Relay output
| Item |
Specification |
| Rated load voltage |
5 to 250V AC, 5 to 30V DC |
| Minimum switching current |
1mA |
| Leak current |
15mA or less |
| Maximum load current |
1 circuit |
2 A (24 V DC, 240V AC) |
| 1 common |
5A |
| Output response time |
OFF → ON |
15 ms (max) |
| ON → OFF |
15 ms (max) |
| Surge removing circuit |
None |
| Fuse |
None |
| Insulation system |
Relay insulation |
| Output display |
LED (green) |
Externally supplied power (for driving the relays) |
Not necessary |
| Contact life |
20,000,000 times (mechanical) 200,000 times (electrical: 2 A) |
| Insulation |
1500V or more (external-internal) 500V or more (external-external) |
| External connection |
Removable type screw terminal block (M3) |
| Circuit diagram |

|
Relay output (8 points / 16 points expansion unit)
| Item |
Specification |
| Rated load voltage |
5 to 250V AC, 5 to 30V DC |
| Minimum switching current |
1mA |
| Leak current |
15mA or less |
| Maximum load current |
1 circuit |
2 A (24 V DC, 240V AC) |
| 1 common |
5A |
| Output response time |
OFF → ON |
15 ms (max) |
| ON → OFF |
15 ms (max) |
| Surge removing circuit |
None |
| Fuse |
None |
| Insulation system |
Relay insulation |
| Output display |
LED (green) |
Externally supplied power (for driving the relays) |
Not necessary |
| Contact life |
20,000,000 times (mechanical) 200,000 times (electrical: 1.5 A) |
| Insulation |
1500V or more (external-internal) 500V or more (external-external) |
| External connection |
Removable type screw terminal block (M3) |
| Circuit diagram |
 |
|